Case study · Atherton
WhisperKOOL 8000 H.E. Repair in Atherton: A Cellar at 68°F, Back to 55°F in 6 Hours
Condensation on the bottles, and a unit that ran but barely cooled. We found a blocked condenser coil, a low charge and a drifting sensor.
Text a photo of your unit- System
- WhisperKOOL 8000 H.E.
- Problem
- Cellar at 68°F for three days
- What we did
- Cleaned, sealed, recharged, recalibrated
- Result
- Back to 55°F within 6 hours
Photos From the Job
Photos from this job. Cropped and resized, nothing retouched.

In the cellarTechnician at the open ceiling unit 
The cellarGlass door, lit racks 
The cellarLit racks and an arched niche 
OutsideThe WhisperKOOL 8000 H.E. condensing unit
What We Found and What We Did
The problem
The homeowner noticed condensation on the bottles and checked the thermometer. The cellar had been at 68°F for three days, against a target of 55°F. The WhisperKOOL 8000 H.E. was running but barely producing cool air.
Our diagnosis
The condenser coil was more than 70% blocked with dust, so the unit could not get rid of its heat. The refrigerant charge was 18% below specification, from a slow leak at a flare fitting on the condenser. The temperature sensor had drifted 4°F from calibration.
What we did
We cleaned the condenser and evaporator coils and repaired the leak at the flare fitting. We evacuated the system and recharged it to WhisperKOOL factory specification. Then we recalibrated the temperature sensor.
The result
The cellar was stable at 55°F within 6 hours, and no wine was damaged. To prevent a repeat, we recommended regular maintenance: condenser cleaning and a refrigerant check. Maintenance is from $485 per visit.
Repair or Replace? It Depends on the Type of System
This unit was repaired. Whether a repair makes sense depends on the type of system and on where the unit sits.
- Repair
Split systems
Any split system (an evaporator at the cellar and a separate condensing unit), factory-built or custom-built on site. We repair these and install new ones.
- Repair or replace
Self-contained units in a cellar
We repair these too. Often a new unit is the better choice: for a repair the unit has to be taken out, then reinstalled and started again. For units older than 8 years we recommend replacement.
- Replace
Cabinet units and the 1800 series
Self-contained units built into wine cabinets, and the CellarPro 1800 series wherever it is installed. We replace these rather than repair them.
Not sure which type you have?
Text us a photo of the unit and its label. We will tell you whether to repair or replace it.
More Projects
Two more wine cellar jobs, among them another one in Atherton, and the work we do outside the cellar.
Case study · AthertonA ducted CellarPro system for a glass wine roomRefrigerant leak and a failed compressor. Replaced with a new CellarPro AH6500 ducted split system.
Case study · Los AltosFailed compressor in a self-contained WhisperKOOLWhisperKOOL 8000 XLT, about 15 years old. Replaced with a WhisperKOOL Extreme 8000ti.
Other work by North Breeze
Need Wine Cellar Service?
Tell us what the cellar is doing and we will call you back. Authorized by WhisperKOOL and CellarPro; we repair split systems of any brand.
- We usually reply within the hour during business hours
- Most visits are the same day
- After-hours emergency service on request
Got it. We will be in touch soon.
We usually reply within the hour during business hours.
If you do not hear from us within the hour during business hours, please call us.
For urgent matters, call (408) 581-2241